Flame-Trol
LFG Specialties "Flame-Trol" controllers are unique in the industry, as all of our controllers come standard with the ability to completely bypass the automatic controls and operate the flare manually.
The Flame-Trol family of
controllers include:
Flame-Trol I (Relay based controller
for utility/candlestick flares)
Features
Ultraviolet Flame Scanner—
provides flame confirmation during automatic start-up and flare safety shutdown upon loss of flame.
Temperature Controller—provides back-up safety shutdown upon loss of flame, turns the blower on when appropriate, turns the pilot fuel off after ideal burning temperature has been reached and features a constant temperature read out. .
Pilot Timer and Failure Indicators—provide control for the propane pilot fuel and provide a failure indicator if the propane is exhausted or fails to achieve proper temperature. .
Down Time Timer—provides the operator with a set time after a shutdown for the system to remain down in order to allow the wellfield to rejuvenate. .
Igniter Timer—provides control of the igniter spark duration.
Manual/Auto Switch—provides the operator the ability to completely bypass the automatic controls and operate manually. This allows the operator to trouble shoot or operate the system in case relays/PLC need repair.
Flame-Trol II (Relay and PLC
controller for enclosed flares)
Same as Flame-Trol I plus:
Features
Energy saving propane pilot that
operates only during the ignition
cycle. .
Flare Chamber Temperature
Controller—monitors and
controls the temperature in the
flare chamber and drives the
automatic air louvers on the flare
stack. Also provides settings
for high and low temperature
shutdowns. .
Ultraviolet Flame Scanner—
provides flame confirmation during
automatic start-up and flare safety
shutdown upon loss of flame. .
Purge Timer—controls the length
of time the purge blower operates
in order to accomplish a complete
purge of the flare chamber. .
Main Header Valve Indicators—
indicate valve fully open or
fully closed. .
Key Lock Switch—a primary
safety, cutting power to the
panel when locked. .
Emergency Shut-Down—a large,
red, panel mounted button that
when pressed will immediately
shut-down the flare, stop the
blower, and close the main
header valve. .
Temperature Recorder—
constantly records the flare
chamber temperature, as well
as one other user defined
parameter such as gas flow. .